Existing Conditions
Click Photo to Learn More

LIBRARY
𝐌𝐞𝐜𝐡𝐚𝐧𝐢𝐜𝐚𝐥 𝐑𝐨𝐨𝐦
The chiller pump has exceeded its median life expectancy and is recommended for replacement. In addition, the equipment was not installed on a housekeeping pad and is not properly elevated above the floor.
The chiller pump has exceeded its median life expectancy and is recommended for replacement. In addition, the equipment was not installed on a housekeeping pad and is not properly elevated above the floor.

LIBRARY
𝐌𝐞𝐜𝐡𝐚𝐧𝐢𝐜𝐚𝐥 𝐑𝐨𝐨𝐦
Air handling units in the mechanical room are at the end of their service life and need replacement to ensure proper ventilation, temperature control, and energy efficiency.
Air handling units in the mechanical room are at the end of their service life and need replacement to ensure proper ventilation, temperature control, and energy efficiency.

LIBRARY
𝐌𝐞𝐜𝐡𝐚𝐧𝐢𝐜𝐚𝐥 𝐑𝐨𝐨𝐦
The vertical fresh air intake shaft requires evaluation for proper airflow, maintenance access, and potential blockages. Inadequate design or obstructions could impact ventilation efficiency and indoor air quality.
The vertical fresh air intake shaft requires evaluation for proper airflow, maintenance access, and potential blockages. Inadequate design or obstructions could impact ventilation efficiency and indoor air quality.

LIBRARY
𝐌𝐞𝐜𝐡𝐚𝐧𝐢𝐜𝐚𝐥 𝐑𝐨𝐨𝐦
Cast iron plumbing in the mechanical room is deteriorating and failing. This creates a risk of leaks, water damage, and potential disruption to building operations if not replaced or repaired.
Cast iron plumbing in the mechanical room is deteriorating and failing. This creates a risk of leaks, water damage, and potential disruption to building operations if not replaced or repaired.

LIBRARY
𝐌𝐞𝐜𝐡𝐚𝐧𝐢𝐜𝐚𝐥 𝐑𝐨𝐨𝐦
Cast iron plumbing in the mechanical room is deteriorating and failing. This creates a risk of leaks, water damage, and potential disruption to building operations if not replaced or repaired.
Cast iron plumbing in the mechanical room is deteriorating and failing. This creates a risk of leaks, water damage, and potential disruption to building operations if not replaced or repaired.

LIBRARY
𝐏𝐫𝐨𝐠𝐫𝐚𝐦 𝐑𝐨𝐨𝐦
Wall in the program room was previously repaired following water infiltration but remains unfinished in case of future leaks. This impacts aesthetics, may reduce durability, and could allow future moisture issues if not properly completed.
Wall in the program room was previously repaired following water infiltration but remains unfinished in case of future leaks. This impacts aesthetics, may reduce durability, and could allow future moisture issues if not properly completed.

LIBRARY
𝐑𝐞𝐬𝐭𝐫𝐨𝐨𝐦
Lower-level restroom is currently functional. This serves as an example of a working facility, though accessibility and capacity for building users should be evaluated relative to overall demand
Lower-level restroom is currently functional. This serves as an example of a working facility, though accessibility and capacity for building users should be evaluated relative to overall demand

LIBRARY
𝐒𝐭𝐚𝐟𝐟 𝐁𝐫𝐞𝐚𝐤𝐫𝐨𝐨𝐦
Evidence of hard water buildup in the staff breakroom plumbing and fixtures. This can affect water quality, reduce fixture lifespan, and require water treatment solutions.
Evidence of hard water buildup in the staff breakroom plumbing and fixtures. This can affect water quality, reduce fixture lifespan, and require water treatment solutions.

LIBRARY
𝐄𝐥𝐞𝐯𝐚𝐭𝐨𝐫 𝐄𝐪𝐮𝐢𝐩𝐦𝐞𝐧𝐭 𝐑𝐨𝐨𝐦
Elevator equipment in the mechanical room requires evaluation for age, functionality, and maintenance needs to ensure safe and reliable vertical transportation throughout the building.
Elevator equipment in the mechanical room requires evaluation for age, functionality, and maintenance needs to ensure safe and reliable vertical transportation throughout the building.

LIBRARY
𝐄𝐥𝐞𝐯𝐚𝐭𝐨𝐫
Elevator does not meet ADA accessibility standards, limiting access for individuals with disabilities and potentially violating building codes or accessibility requirements.
Elevator does not meet ADA accessibility standards, limiting access for individuals with disabilities and potentially violating building codes or accessibility requirements.

LIBRARY
𝐄𝐚𝐬𝐭 𝐄𝐧𝐭𝐫𝐚𝐧𝐜𝐞/𝐌𝐚𝐢𝐧 𝐄𝐧𝐭𝐫𝐲
Egress lighting at the entry has failed and replacement parts are no longer available. This creates safety and security concerns for staff and visitors, as well as potential non-compliance with code requirements.
Egress lighting at the entry has failed and replacement parts are no longer available. This creates safety and security concerns for staff and visitors, as well as potential non-compliance with code requirements.

LIBRARY
𝐄𝐚𝐬𝐭 𝐄𝐧𝐭𝐫𝐚𝐧𝐜𝐞/𝐌𝐚𝐢𝐧 𝐄𝐧𝐭𝐫𝐲
Egress lighting at the entry has failed and replacement parts are no longer available. This creates safety and security concerns for staff and visitors, as well as potential non-compliance with code requirements.
Egress lighting at the entry has failed and replacement parts are no longer available. This creates safety and security concerns for staff and visitors, as well as potential non-compliance with code requirements.

LIBRARY
𝐌𝐚𝐢𝐧 𝐄𝐧𝐭𝐫𝐲 𝐑𝐨𝐨𝐟
Exterior façade at the main entry roof is cracking, and roof flashing is not properly sealed. This creates potential water intrusion, structural damage, and increased maintenance needs.
Exterior façade at the main entry roof is cracking, and roof flashing is not properly sealed. This creates potential water intrusion, structural damage, and increased maintenance needs.

LIBRARY
𝐌𝐚𝐢𝐧 𝐄𝐧𝐭𝐫𝐲 𝐑𝐨𝐨𝐟
Roof flashing at the main entry is damaged, creating potential for water intrusion, structural damage, and increased maintenance needs if not repaired or replaced.
Roof flashing at the main entry is damaged, creating potential for water intrusion, structural damage, and increased maintenance needs if not repaired or replaced.

LIBRARY
𝐍𝐨𝐫𝐭𝐡 𝐖𝐚𝐥𝐥
Water is infiltrating from the roof system along the north wall. This may lead to interior damage, mold growth, and structural deterioration if not addressed.
Water is infiltrating from the roof system along the north wall. This may lead to interior damage, mold growth, and structural deterioration if not addressed.

LIBRARY
𝐖𝐞𝐬𝐭 𝐖𝐚𝐥𝐥 - 𝐓𝐡𝐫𝐨𝐮𝐠𝐡𝐨𝐮𝐭 𝐅𝐚𝐜𝐢𝐥𝐢𝐭𝐲
Foundation cracks are present along the west wall as well as throughout the facility. These may compromise structural integrity, lead to water intrusion, and require monitoring or repair to prevent further deterioration.
Foundation cracks are present along the west wall as well as throughout the facility. These may compromise structural integrity, lead to water intrusion, and require monitoring or repair to prevent further deterioration.

LIBRARY
𝐖𝐞𝐬𝐭 𝐖𝐚𝐥𝐥 - 𝐓𝐡𝐫𝐨𝐮𝐠𝐡𝐨𝐮𝐭 𝐅𝐚𝐜𝐢𝐥𝐢𝐭𝐲
Foundation cracks are present along the west wall as well as throughout the facility. These may compromise structural integrity, lead to water intrusion, and require monitoring or repair to prevent further deterioration.
Foundation cracks are present along the west wall as well as throughout the facility. These may compromise structural integrity, lead to water intrusion, and require monitoring or repair to prevent further deterioration.

LIBRARY
𝐒𝐨𝐮𝐭𝐡 𝐖𝐚𝐥𝐥/𝐑𝐨𝐨𝐟
Roof along the south wall is sagging, which may indicate structural weakness or deterioration. This condition poses safety risks and requires assessment and repair to prevent further damage or potential collapse.
Roof along the south wall is sagging, which may indicate structural weakness or deterioration. This condition poses safety risks and requires assessment and repair to prevent further damage or potential collapse.

LIBRARY
𝐄𝐱𝐭𝐞𝐫𝐢𝐨𝐫 𝐒𝐨𝐮𝐭𝐡 𝐖𝐚𝐥𝐥 𝐃𝐨𝐨𝐫
Door on the south wall is inoperable, limiting access, egress, and operational functionality. Repair or replacement is required to restore proper use.
Door on the south wall is inoperable, limiting access, egress, and operational functionality. Repair or replacement is required to restore proper use.

LIBRARY
𝐀𝐝𝐦𝐢𝐧𝐢𝐬𝐭𝐫𝐚𝐭𝐢𝐯𝐞 𝐎𝐟𝐟𝐢𝐜𝐞
Fire panel in administrative offices triggers random alarms. This creates safety concerns, potential false alarm responses, and indicates the panel may be malfunctioning or outdated and requires repair or replacement.
Fire panel in administrative offices triggers random alarms. This creates safety concerns, potential false alarm responses, and indicates the panel may be malfunctioning or outdated and requires repair or replacement.

LIBRARY
𝐀𝐝𝐦𝐢𝐧𝐢𝐬𝐭𝐫𝐚𝐭𝐢𝐯𝐞 𝐎𝐟𝐟𝐢𝐜𝐞
Main office area does not provide sufficient space for administrative staff. Limited space reduces workflow efficiency, impacts staff productivity, and may not accommodate future growth or equipment needs.
Main office area does not provide sufficient space for administrative staff. Limited space reduces workflow efficiency, impacts staff productivity, and may not accommodate future growth or equipment needs.

LIBRARY
𝐌𝐚𝐢𝐧 𝐋𝐞𝐯𝐞𝐥 - 𝐆𝐞𝐧𝐞𝐫𝐚𝐥 𝐂𝐨𝐥𝐥𝐞𝐜𝐭𝐢𝐨𝐧
Shelving in the general collection area cannot be rearranged, limiting flexibility for space reconfiguration and collection growth. Additionally, the shelves are worn and damaged, reducing functionality and aesthetics.
Shelving in the general collection area cannot be rearranged, limiting flexibility for space reconfiguration and collection growth. Additionally, the shelves are worn and damaged, reducing functionality and aesthetics.

LIBRARY
𝐌𝐚𝐢𝐧 𝐋𝐞𝐯𝐞𝐥 𝐑𝐞𝐬𝐭𝐫𝐨𝐨𝐦
Main floor restroom is heavily used and shows signs of wear. This may affect hygiene, user experience, and maintenance requirements. Upgrades or repairs are needed to maintain functionality and safety.
Main floor restroom is heavily used and shows signs of wear. This may affect hygiene, user experience, and maintenance requirements. Upgrades or repairs are needed to maintain functionality and safety.

LIBRARY
𝐌𝐚𝐢𝐧 𝐋𝐞𝐯𝐞𝐥 𝐑𝐞𝐬𝐭𝐫𝐨𝐨𝐦
Entrance to the main level restroom does not meet ADA accessibility standards, limiting access for individuals with disabilities and potentially violating code requirements.
Entrance to the main level restroom does not meet ADA accessibility standards, limiting access for individuals with disabilities and potentially violating code requirements.

LIBRARY
𝐌𝐚𝐢𝐧 𝐋𝐞𝐯𝐞𝐥 - 𝐆𝐞𝐧𝐞𝐫𝐚𝐥 𝐂𝐨𝐥𝐥𝐞𝐜𝐭𝐢𝐨𝐧
Roof leaks are allowing water into the interior ceiling tiles in the general collection area. This can cause damage to finishes, create safety hazards, and potentially affect collections if not addressed.
Roof leaks are allowing water into the interior ceiling tiles in the general collection area. This can cause damage to finishes, create safety hazards, and potentially affect collections if not addressed.